Digital Inputs / Outputs
Digital inputs (terminal strips X14, X15, X16) | |
|---|---|
Remote control, remote precision adjustment EFE 1000 (terminal 9 – 30) | < 4 V⎓ (low), > 8 V⎓ (high) |
Controller interlock | < 4 V⎓ (low), > 8 V⎓ (high) |
Galvanic isolation | None! |
Connection | Internally on the spring-cage terminal block |
Digital outputs (terminal strips X16)* | |
|---|---|
Voltage | Max. 24 V⎓ |
Current | Max. 0.2 A |
Current supply max. | Max. Σ +24 V⎓: 300 mA |
* not available with product variants ekr CON 600.1 and ekr CON 600 net XX.1 (see Product Variants)