Connecting the Cables

Cables up to 0.75 mm2

Use core end sleeves with collar for the connections (DIN 46228/Part 4).

  • The crimping must be carried out gas tight (no cross-crimping).
  • There must be no gaps between the conductor and the core end sleeve
  • The length of the metal sleeves fitted on the core end sleeve must be at least 8 mm.
For crimping, we recommend the crimping pliers VarioCrimp-4-Zange 206-204 from Wago.

Cables from 0.75 mm2 to max. 1.5 mm2

Connect the cables without core end sleeve.

  • For fine and multi-core cables and for fine-wired cables, whose kink resistance is not sufficient due to the small diameter, in order to overcome the contact force of the clamping springs, the clamp must be properly opened using a screwdriver.

 

  • After connecting, in both cases check the correct fit of the cable.