Setting DIL Switch S5

Using DIL switch S5, carry out the following settings:

  • Reverse the actuator motor rotation direction
  • Adjust the assignment of sensors
  • Activate the remote control
  • Configure CAN bus parameters

 

Rotate the smartphone by 90 degrees to show the entire table.

DIL Switch

Status

Function

S5.1

 

Reversing the motor rotation direction
(see also function of DIL switch S4.1 and S4.2)

S5.2

OFF

Analogue input for sensor 1 deactivated
(connection of a digital sensor via CAN bus)

ON

Analogue input for sensor 1 activated
(connection of an analogue sensor via CAN bus)

S5.3

OFF

Analogue input for sensor 2 deactivated
(connection of a digital sensor via CAN bus)

ON

Analogue input for sensor 2 activated
(connection of an analogue sensor via CAN bus)

S5.4

 

Invert the sensor signal for sensor 1 and sensor 2

S5.5

OFF

Remote control inputs activated

ON

Remote control inputs deactivated

S5.6

OFF

Connector socket X101 is configured as internal BST CAN bus, i.e. it behaves in the same manner as connector sockets X100, X102, X103, X104

ON

Connector socket X101 is configured as external CAN bus (networked)

 

Rotate the smartphone by 90 degrees to show the entire table.

DIL Switch

Baud Rate

Note

S5.7

S5.8

OFF

OFF

500 kBit

Applies only for connector socket X101 with galvanic separation. The connector sockets X100, X102, X103, X104 are always operated with 500 Kbit and without galvanic separation.

ON

OFF

125 kBit

OFF

ON

250 kBit

ON

ON

1 Mbit